App Note: Use current or voltage in analog transducer readings?

When choosing an analog measurement transducer for a variety of instrumentation monitoring applications including machine monitoring, quality assurance, and more, you will be given a choice of signal types.

The most common signals for these transducers are either voltage (0-5 volts DC, or 0-10 volts DC) or current (generally 4-20 milliamps). Both types are low-cost and easy to find, and both have advantages and disadvantages depending on the environment in which they are being used.

Applications Specialists at CAS DataLoggers explore both the pros and cons of these two analog signals.

DC Voltage (0-5v, 0-10V)
DC voltage is a very basic analog signal which gives you excellent resolution, is easy to connect and troubleshoot, and is well suited to lab environments. The sensors which use a voltage output tend to be quick and easy to connect. They require an input excitation voltage and have an easy to identify output wire carrying the measured signal.
 
However, a voltage signal is not a good fit if you are planning on using it in an industrial environment. Even when using shielded wire, the signal is highly susceptible to interference from high voltage AC, motors, pumps, relays, etc. The signal is also susceptible to voltage drops on log runs of signal wire.

DC Current (4-20mA)
In contrast, a DC current loop offers several advantages in industrial settings. This signal is not as susceptible to electrical interference from high voltage AC, motors, pumps, or relays, nor is it susceptible to signal loss due to the length of the wiring run (voltage drop). A 4-20mA loop can also power multiple devices using one excitation source and requires much fewer wires. Additionally, a 4-20 mA signal offers fairly easy fault detection because its ‘0’ point is at 4mA, so if a negative reading is shown in the scaled readings, there’s likely a problem with the signal.

However, a 4-20mA signal will not give you the same resolution as a voltage signal so it is not necessarily recommended for use in a lab environment. Another drawback of a 4-20mA signal is that you will generally require shunt resistors to take a reading on most data logging equipment.

While there are many other considerations to take into account when choosing a transducer, environment and signal distance should be your main factors.

This outline will hopefully have given you a good basis for the best signal choice between voltage and current.

More company info here.

1 comment on “App Note: Use current or voltage in analog transducer readings?

  1. kjsldjkf
    July 8, 2014

    Best printers in Canada: Canada Printer Companies

    Best sticker printing companies: custom sticker print quote | Print Custom Stickers | Sticker printing company. They provided the best quality and price out there.

    Best print trader: Lowest Price Printing Wholesale

    Other great printing services: Print Services | Custom Printing Services | Print Companies | Best Printing Company

    Best printers in U.S.A: Atlanta Printer | Boston Printer | Chicago Printer | Arizona Printer | Miami Printer | New York Printer

    Best printer management software: Print Company Software

Leave a Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.